23
Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com 1 TSM-/TSE-/TF- Atex TSK-Atex TSA - Atex Lesen Sie die Bedienungsanleitung vor dem Gebrauch des Gerätes gründlich durch, insbesondere die Hinweise unter Gliederungspunkt 2 und 7.1. Andernfalls könnten Gesundheits- oder Sachschäden auftreten. Bühler Technologies GmbH haftet nicht für unsachgemäßen Gebrauch. Please read this instruction manual carefully before use, especially the safety remarks in chapter 12 and 17.1. Otherwise injuries to health and properties cannot be excluded. Bühler Technologies GmbH can not be made responsible for failures due to misuse of the product or unauthorized modifications. E-mail: [email protected] BX140010

Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Embed Size (px)

Citation preview

Page 1: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

1

TSM-/TSE-/TF- Atex TSK-Atex TSA - Atex

Lesen Sie die Bedienungsanleitung vor dem Gebrauch des Gerätes gründlich durch, insbesondere die Hinweise unter Gliederungspunkt 2 und 7.1. Andernfalls könnten Gesundheits- oder Sachschäden auftreten. Bühler Technologies GmbH haftet nicht für unsachgemäßen Gebrauch. Please read this instruction manual carefully before use, especially the safety remarks in chapter 12 and 17.1. Otherwise injuries to health and properties cannot be excluded. Bühler Technologies GmbH can not be made responsible for failures due to misuse of the product or unauthorized modifications.

E-mail: [email protected] BX140010

Page 2: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

2

Inhaltsverzeichnis Seite

1. Einleitung 4

2. Wichtige Hinweise 4

2.1. Allgemeine Gefahrenhinweise 4-5

3. Erläuterungen zum Typenschild 6

4. Produktbeschreibung 6

4.1. Allgemeine Beschreibung 6

4.2. Lieferumfang 7

5. Transport und Lagerungsvorschriften 7

6. Aufbauen und Anschließen 7

6.1. Montage 7

6.2. Elektrische Anschlüsse 7

6.2.1 Eigensicherer Anschluß 8

7. Betrieb und Wartung 8

7.1. Warnhinweise 8-9

7.2. Betrieb 9

7.3. Wartung 9

8. Fehlersuche und Beseitigung 10

9. Instandsetzung und Entsorgung 10

9.1. Entsorgung 10

10. Beständigkeitsliste 11

21. Anhang 19

21.1 Auswahl der Anschlußbelegungen 19

21.2 Informationen zum PA-Anschluß 20-21

21.3 Technische Daten zu Temperaturkontakten bzw. Pt100 21

21.4 Technische Daten zu den Steckern 22

21.5 Technische Daten zu den Temperaturschaltern (-fühlern) 22

21.6 Konformitätserklärung 23

E-mail: [email protected] BX140010

Page 3: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

3

Contens Seite

11. Introduction 12

12. Important advice 12

12.1. General indication of risk 12-13

13. Explanation of the type plate 14

14. Product description 14

14.1. General description 14

14.2. Included items in delivery 15

15. Transport and storing regulations 15

16. Installation and connection 15

16.1. Mounting 15

16.2. electrical connecting 15

16.2.1 Intrinsically safe connection 15

17. Operation and Maintenance 16

17.1. Indication of risk 16-17

17.2. Operation 17

17.3. Maintenance 17

18. Trouble shooting and elimination 17

19. Repair and disposal 17

19.1. Disposal 17

20. List of chemical resistance 18

21. Appendix 19

21.1 wiring diagrams 19

21.2 Informations about PA connection 20-21

21.3 Technical datas temperature contact / Pt100 21

21.4 Technical datas connectors 22

21.5 Technical datas temperature switch (-sensor) 22

21.6 Declaration of conformity 23

E-mail: [email protected] BX140010

Page 4: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

4

1. Einleitung Bei den Temperaturfühlern TF...-ATEX und Temperaturschaltern TS... –ATEX handelt es sich nach DIN EN 50020 um einfache elektrisches Betriebsmittel ohne eigene Spannungsquelle welche für den Tankeinbau oder (ausschließlich bei Typ TSA) für den Einbau in Rohrleitungssysteme und Kühlregistern bestimmt sind.

Bei eigensicherem Anschluß können sie im explosionsgefährdeten Bereich der Zonen 1 (Gruppe IIC) installiert werden. Sie dienen hierbei zur Temperaturüberwachung von Fluiden.

Diese Bedienungsanleitung beschreibt mehrere Temperaturschalter (Fühler)-Typen zusammen, da viele Beschreibungen gleich oder ähnlich sind.

Welchen Temperaturschalter (-fühler) Sie vor sich haben, ersehen Sie aus dem Typenschild. Auf diesem finden Sie neben der Auftragsnummer auch die Artikelnummer und Typbezeichnung. Sofern für einen Typ Besonderheiten gelten, sind diese in der Bedienungsanleitung gesondert beschrieben.

Bitte überprüfen Sie vor Einbau der Betriebsmittel, ob die genannten technischen Daten den Anwendungs-parametern entsprechen. Berücksichtigen Sie außerdem die zutreffenden Anforderungen der EN 60079-14.

Überprüfen Sie ebenfalls, ob alle zum Lieferumfang gehörende Teile vollständig vorhanden sind.

Beachten Sie beim Anschluß die Kennwerte der Betriebsmittel und bei Ersatzteilbestellungen die richtigen Ausführungen.

2. Wichtige Hinweise Der Einsatz der Geräte ist nur zulässig, wenn:

- das Produkt unter den in der Bedienungs- und Installationsanleitung beschriebenen Bedingungen, dem Einsatz gemäß Typenschild und für Anwendungen, für die es vorgesehen ist, verwendet wird.

- die Betriebsmittel in eigensicheren Stromkreisen betrieben werden (DIN EN 60079-14 beachten)

- Überwachungsvorrichtungen/ Schutzvorrichtung korrekt angeschlossen sind.

- die Service- und Reparaturarbeiten von Bühler Mess- und Regeltechnik GmbH durchgeführt werden.

- Originalersatzteile verwendet werden.

Diese Bedienungsanleitung ist Teil der Betriebsmittel. Der Hersteller behält sich das Recht vor, die Leistungs-, die Spezifikations- oder die Auslegungsdaten ohne Vorankündigung zu ändern.

2.1. Allgemeine Gefahrenhinweise Beachten Sie unbedingt die für den Einbauort relevanten Sicherheitsvorschriften und allgemeinen gültigen Regeln der Technik.

Beachten Sie ebenfalls die Prozeßbedingungen und sorgen Sie insbesondere bei der Wartung dafür, daß Sie sich vor giftigen Gasen schützen. Gegebenenfalls Handschuhe, Atem- und Gesichtsschutz tragen!

- Auf die Einhaltung der zulässigen Daten und Einsatzbedingungen achten.

- Bei der Entsorgung bitte die gesetzlichen Regelungen beachten.

- Bewahren Sie die Anleitung für den späteren Gebrauch auf.

E-mail: [email protected] BX140010

Page 5: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

5

Achtung ! Atex-Version

!

Nicht in dieser Anleitung beschriebene Reparaturen an den Temperaturschaltern (-fühlern) dürfen nur von Bühler autorisiertem Personal ausgeführt werden.Führen Sie nur Umbau-, Wartungs- oder Montagearbeiten aus, die in dieser Bedienungs- und Installationsanleitung beschrieben sind. Verwenden Sie nur Original-Ersatzteile.

Achtung !

Bei Arbeiten an elektrischen Betriebsmitteln diese vom Stromnetz trennen. Sicherstellen, daß das Betriebsmittel nicht unbeabsichtigt wieder unter Spannung gesetzt werden kann.

Achtung !

Temperaturkontakte und Pt100 Sensoren sind eigensicher anzuschließen. Anforderungen der DIN EN 60079-14 sind dringend zu beachten.

!

Achtung !

!

Störung vorbeugen und dadurch Personen- und Sachschäden vermeiden. Der für die Anlage Verantwortliche muss sicherstellen, dass: - Sicherheitshinweise und Betriebsanleitungen verfügbar sind und eingehalten werden. - Unfallverhütungsvorschriften der Berufsgenossenschaften beachtet werden: Allgemeine Vorschriften“ (VBG 1) und „Elektrische Anlagen und Betriebsmittel (VBG 4)“. - Betriebsbedingungen und technische Daten gemäß Auftrag beachtet werden. - Schutzeinrichtungen verwendet werden und vorgeschriebene Wartungsarbeiten durchgeführt werden.

Das Errichten elektrischer Anlagen in explosionsgefährdeten Bereichen erfordert in Deutschland die Beachtung folgender Vorschriften:

- EN 60079-14 / DIN VDE 0165 T1 „Errichten elektrischer Anlagen in explosionsgefährdeten Bereichen“

- EN 50281-1-2 / DIN VDE 0165 T2 „Elektrische Betriebsmittel zur Verwendung in Bereichen mit brennbarem Staub, Auswahl, Errichtung und Instandhaltung.

- ElexV „Verordnung über elektrische Anlagen in explosionsgefährdeten Räumen“ Im Ausland sind die entsprechenden Landesvorschriften zu beachten.

E-mail: [email protected] BX140010

Page 6: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

6

3. Erläuterungen zum Typenschild

Serien Nr., Artikel Nr. und Baujahr

Hersteller mit Anschrift Typbezeichnung

Zündschutzkennzeichnung

Technologies GmbHHarkortstr.29, D-40880 Ratingen

Made in Germany

II 2G EEx ib IIC T5 TSM- ATEX

A345678/001 4622220X2 Bj:2003 30V DC, 90mA / File Ref 2552

Spannung / Tech. File Ref.

II 2 G EEx ib IIC T5

Gerätegruppe

Atmosphäre G = Gas

Zündschutzart

Explosionsgruppe

Temperaturklasse Gerätekategorie 2 (für Zone 1 )

Beispiel für eine Zündschutzkennzeichnung

4. Produktbeschreibung

4.1. Allgemeine Beschreibung Diese Bedienungs- und Installationsanleitung gilt für die ATEX Temperaturschalter (-fühler) TSx-ATEX und TFx-ATEX Bei den o.g. Temperaturschaltern (-fühler) handelt es sich gemäß EN 50020 um einfache elektrisches Betriebsmittel ohne eigene Spannungsquelle. Bei Einsatz in explosiongefährdeten Bereichen dürfen alle o.g. Typen nur innerhalb eigensicherer Stromkreise betrieben werden (Anforderungen dieser Anleitung und der DIN EN 60079-14, sowie technische Spezifikationen beachten). Die Betriebsmittel können zur Temperaturüberwachung von Fluiden eingesetzt werden. Hierbei befindet sich ein Meßrohr innerhalb des Mediums. Temperaturkontakte (Bimetallscheiben-Thermostat) oder Pt100 Sensoren sind innerhalb des Meßrohrs angeordnet. Die Montage der Betriebsmittel erfolgt über ein Außengewinde am Temperatur-schalter (-fühler).

Temperaturfühler TF-M-Pt100 / TF-E-Pt100: Die Temperaturfühler Typ TF verwenden einen Pt100 Temperatursensor nach DIN / IEC 751 Klasse B zur Erzeugung eines temperaturabhängigen Widerstandssignals. Der Pt100 Sensor ist an der tiefsten Stelle des Fühlerrohrs angebracht, um immer einen ausreichenden Kontakt mit dem zu messenden Medium zu gewährleisten.

Bi-Metall Temperaturschalter TSM / TSE / TSK / TSA: Die Temperaturfühler TS verwenden einen Bimetall-Temperaturschalter zur Signalisierung eines vorher festgelegten Temperaturwertes. Gegenüber der Standardversion TSM sind die Versionen TSK und TSA mit Bimetallschaltern geringerer Hysterese ausgestattet. Weiterhin ist die Version TSA speziell für die Installation in Rohrleitungssystem und Kühlregistern ausgelegt. Der Bimetallschalter ist an der tiefsten Stelle des Fühlerrohrs angebracht, um immer einen ausreichenden Kontakt mit dem zu messenden Medium zu gewährleisten.

E-mail: [email protected] BX140010

Page 7: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

7

4.2 Lieferumfang - Temperaturschalter TSM-Atex, TSE-Atex und TSA-Atex sowie

- Temperaturfühler TF-M-Atex und TF-E-Atex

Menge Artikel-Nr.

1.) Bedienungsanleitung BX140010 1 9032012

2.) Elastische Profildichtung G1/2 (NBR) 1 1120101

- Temperaturschalter TSK-Atex

1.) Bedienungsanleitung BX140010 1 9032012

2.) Elastische Profildichtung G3/4 (NBR) 1 1120102

5. Transport und Lagerungsvorschriften Die Betriebsmittel nur in der Originalverpackung oder einem geeigneten Ersatz transportieren. Bei längerer Nichtbenutzung sind die Temperaturschalter (-fühler) gegen Feuchtigkeit und Wärme zu schützen. Die Temperaturschalter (Fühler) müssen in einem überdachten, trockenen, vibrations- und staubfreien Raum bei einer Temperatur von –20°C bis +40°C aufbewahrt werden.

6. Aufbauen und Anschließen

6.1. Montage Die Temperaturschalter (-fühler) werden komplett montiert angeliefert und können mittels des Einschraubge-windes befestigt werden.

Das maximale Anzugsmoment des Einschraubgewindes beträgt 25 Nm. Beim Einbau auf eine saubere und ebene Dichtfläche achten. Darauf achten, daß der Temperaturfühler/Schalter nur in das dafür passende Gewinde eingeschraubt wird. Die Abdichtung erfolgt über einen elastischen Dichtring. Andere Dichtmittel sind nicht erforderlich. Die Anschlussbelegungen und technischen Daten finden Sie ab Kapitel 21, nach dem englischen Teil.

6.2. Elektrische Anschlüsse (Eigensicher) Die Anschlußbelegung und technischen Daten für Ihre Temperaturschalter (-fühler) entnehmen Sie den Auswahltabellen auf Seite 19. Die elektrischen Daten entnehmen Sie jeweils dem dazu gehörigem Datenblatt ihres Temperaturschalters (-fühlers) am Ende dieser Anleitung. Beachten Sie, daß über den vorhandenen externen PA-Anschluß jeder Temperaturschalters (-fühler) mit dem geerdeten Tankbehälter verbunden werden muß. Achtung !

!

Der Anschluß darf nur von geschultem Fachpersonal vorgenommen werden. Auf korrekte Spannungsversorgung achten. Örtliche Vorschriften beachten.

E-mail: [email protected] BX140010

Page 8: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

8

6.2.1. Eigensicherer Anschluß Alle Temperaturkontakte und gegebenenfalls Pt100 Temperatursensoren dürfen gemäß EN 60079-14 nur in eigensicheren Stromkreisen betrieben werden. Für Niveau- und Temperaturkontakte sind dabei Maximalströme Imax = 90 mA bei einer Versorgungsspannung Umax bis zu 30VDC zulässig. Pt100 Temperatursensoren dürfen maximal mit einem Meßstrom von 1mA belastet werden (max. Eingangs-leistung Pi = 0.14mW). Achtung !

!

Eigensicherheit Bei Verwendung der Betriebsmittel in gasexplosionsgefährdeten Bereichen sind diese nur in eigensicheren Stromkreisen zu betreiben. (DIN EN 60079-14 sowie Spezifikationen in dieser Anleitung beachten!)

7. Betrieb und Wartung

7.1 Warnhinweise

Achtung !

!

Die Temperaturschalter (-fühler) dürfen nicht außerhalb ihrer Spezifikationen betrieben werden.

Achtung !

!

Nicht in dieser Anleitung beschriebene Reparaturen an den Temperaturschaltern (-fühlern) dürfen nur von Bühler autorisiertem Personal ausgeführt werden. Führen Sie nur Umbau-, Wartungs- oder Montagearbeiten aus, die in dieser Bedienungs- und Installationsanleitung beschrieben sind. Verwenden Sie nur Original-Ersatzteile.

Achtung !

Elektrische Anschlüsse Bei Arbeiten an elektrischen Betriebsmitteln diese vom Stromnetz trennen. Sicherstellen, daß diese Betriebsmittel nicht unbeabsichtigt wieder unter Spannung gesetzt werden können. Anschluß darf nur von geschultem Fachpersonal vorgenommen werden. Auf korrekte Spannungsversorgung achten!

Achtung !

!

Eigensicherheit Bei Verwendung der Temperaturschalter (-fühler) in gasexplosionsgefährdeten Bereichen sind diese nur in eigensicheren Stromkreisen zu betreiben. (DIN EN 60079-14 sowie die Spezifikationen in dieser Anleitung beachten!)

Achtung !

Ätzend Sorgen Sie bei Montage- und Wartungsarbeiten dafür, daß Sie sich vor giftigen / ätzenden Gasen oder Flüssigkeiten schützen. Gegebenenfalls Handschuhe, Atem- und Gesichts-schutz tragen.

E-mail: [email protected] BX140010

Page 9: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

9

Achtung !

!

Bei Durchführung von Wartungsarbeiten jeglicher Art müssen die relevanten Sicherheits- und Betriebsbestimmungen beachtet werden.

Achtung !

!

Elektrostatische Aufladung (Funkenbildung)! Gehäuseteile aus Kunststoff und Aufkleber nur mit feuchtem Tuch reinigen (abreiben).

Achtung !

!

Elektrostatische Entladungen Die Betriebsmittel dürfen nur dort eingesetzt werden, wo es beim Normalbetrieb nicht zu häufigen zündfähigen, elektrostatischen Entladungen kommen kann.

Achtung !

!

Funkenbildung ! Das Betriebsmittel ist vor externen Schlageinwirkungen zu schützen.

7.2 Betrieb Kontrollieren Sie vor Inbetriebnahme: - die Elektroanschlüsse auf Nichtbeschädigung und korrekte Montage. - daß der Temperaturschalter (-fühler) eigensicher angeschlossen ist - daß keine Teile der Temperaturschalter (-fühler) demontiert sind - daß Schutz- und Überwachungsvorrichtungen vorhanden und funktionsfähig sind (z.B.Trennschaltverstärker). - die Umgebungsparameter und technischen Spezifikationen (z.B.: Imax, Umax, Pi) eingehalten werden. - ob die elektrischen Anschlüsse fest angezogen und ob die Überwachungseinrichtungen vorschriftsmäßig angeschlossen und eingestellt sind! - ob Schutzmaßnahmen durchgeführt sind; Erdung! - ob Anschlußstecker verschlossen sind und die Leitungseinführungen sachgemäß abgedichtet wurden. - Anforderungen der EN 60079-14 erfüllt werden. Bitte Beachten Sie die technischen spezifikationen der Temperaturschalter (-fühler) sowie die Anschluß-diagramme am Ende der Anleitung. Beachten sie außerdem dringend die Warnhinweise in Kapitel 7.1. 7.3 Wartung Wenn die Geräte nach der vorstehenden Anleitung eingebaut und angeschlossen wurden, ist eine regelmäßige Wartung nicht erforderlich.

E-mail: [email protected] BX140010

Page 10: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

10

8. Fehlersuche und Beseitigung Achtung !

!

Bei Auftreten einer Störung ist der Temperaturschalter (-fühler) sofort auszuschalten und darf bis zur Beseitigung der Störung nicht mehr in Betrieb genommen werden.

9. Instandsetzung und Entsorgung Sollte ein Fehler beim Betrieb auftreten, wenden Sie sich bitte an unseren Service

Tel.: +49-(0)2102-498955 oder Ihre zuständige Vertretung.

Ist nach Beseitigung eventueller Störungen und nach Einschalten der Netzspannung die korrekte Funktion nicht gegeben, muß das Gerät durch den Hersteller überprüft werden. Bitte senden Sie den Temperatur-schalter (-fühler) zu diesem Zweck in geeigneter Verpackung an:

Bühler Technologies GmbH - Service – Harkortstraße 29 D-40880 Ratingen

9.1. Entsorgung Bei der Entsorgung sind die gesetzlichen und Normenregelungen im Anwenderland zu beachten.

E-mail: [email protected] BX140010

Page 11: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS- ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

11

10. Beständigkeitsliste

Material HLP / HVLP HFA HFC HFD-R HFD-U HETG HEES

Aluminium, ungeschützt j n*1 j j j j j

Aluminium, eloxiert j j j j j j j

Stahl schwarz St37 j n*1 j j j j j

Stahl verzinkt j n*1 n n n n n Stahl verzinkt – chromatisiert j j j n n j j

GG-Guß j n j j j j j

GGG-Guß j n j j j j j

Edelstahl 1.4301 j j j j j j j

Polyamid 6.6 j j j j j*5 j j

Zinn j j n*5 n n

Messing j n*1 n *1 j j j HI 16 (Grundierung blau)

TGIC-PET-Pulver j n j j j

Material HEPG Kerosin Skydrol DOT 4 Methanol Ethanol Aluminium, ungeschützt j n j*5 n j

Aluminium, eloxiert j j j*5 n j

Stahl schwarz St37 j j j*5

Stahl verzinkt j n j*5 Stahl verzinkt – chromatisiert j j j*5

GG-Guß j j

GGG-Guß j j

Edelstahl 1.4301 j j j*5 j j

Polyamid 6.6 j j j*5

Zinn n j

Messing j j*5 HI 16 (Grundierung blau) n

TGIC-PET-Pulver n n *1 = bedingt beständig, *5 = Angabe vom Öllieferant

E-mail: [email protected] BX140010

Page 12: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

12

11. Introduction Temperature switches (sensors) are simple apparatuses according to DIN EN 50020 made for tank top mounting or (only Type TSA) installation in tube systems and cooling matrices. In case of intrinsically safe connection they can be used in Zone 1 (group IIC) of Ex-areas. They are made for temperature monitoring of fluids within a reservoir. This manual is suitable for all temperature switches (sensors) due to similarities of the equipment. You can find the temperature switches (sensors) type on the type plate. There is the order number and also an article number, type marking and Ex-designation. If there are special instructions for a certain type, they are described in the manual. Before mounting please check that the technical specification of the temperature switches (sensors) correspond to the parameters of your application. Regard the specific limits of the equipment. Please take care for the requirements of EN 60079-14 and directive 94/9/EC. Please only order the spare parts which matching the equipment type.

12. Important advice Operation of the temperature switch (sensor) is only valid, when:

- the product is used under the conditions described in the installation- and operation instruction.

- the equipment is connected intrinsically safe ( take care of EC directives 94 / 9 EC and EN 60079-14)

- supervision and protection installations are properly connected.

- service and repair is carried out by Bühler Technologies GmbH (unless described in this manuel).

- only orginal spare parts are used.

This manual is part of the temperature switches (sensors). The manufacturer keeps the right to modify specifications without advanced notice.

12.1. General indication of risk Check all relevant safety regulations and technical indications for the specific installation place.

Regard also the process conditions and make sure that the user is protected against harmful gases,

particularly during maintenance. If necessary wear protective gloves, gas mask and face protector!

- Take care of the performance limits (see drawing of probe type).

- For disposal please regard the corresponding laws.

- Keep this manual for later use. Use equipment only in areas where ignitable electrostatic discharges can not occur frequently during normal operation.

E-mail: [email protected] BX140010

Page 13: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

13

Attention ! Atex-version

!

Any manipulation on the temperature switch (sensor) which is not described in this manual should only be excecuted by Bühler authorizised staff. Only perform modification, servicing or mounting which are described in the manual. Only use original spare parts. .

Attention !

Disconnect the electrical equipment from power supply. Make sure that the equipment cannot be reconnected with mains supply.

Attention !

!

temperature contacts as well as Pt 100 sensors must be connected intrinsically safe. Take care of EN 60079-14 and directive 94 / 9 / EC.

Attention !

!

Prevent failures and by this damage to persons and properties. The person who is responsable for the system must secure, that: - safety and operation instructions are accessible and followed. - local safety regulations and standard are obeyed. - operation conditions and technical data are considered in accordance to the purpose. - Safety installations are used and the prescripted maintenance is performed. - the local regulations for electric installations in explosion ambient should be obeyed. - take care of EC directives 94 / 9 EG

E-mail: [email protected] BX140010

Page 14: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

14

13. Explanation of the type plate

Order-no./position and part-no.

address type description

type of protection

Technologies GmbHHarkortstr.29, D-40880 Ratingen

Made in Germany

II 2G EEx ib IIC T5 TSM- ATEX

A345678/001 4622220X2 Bj:2003 power supply / tech. File ref. 30V DC, 90mA / File Re 2552

II 2 G EEx ib IIC T5

Equipment group

Atmosphere G = gas

Ignition source protection

Ex sub division

Temperature class

Example of a EX designation

Category 2 ( zone 1 )

14. Product description

14.1. General description This manual is suitable for temperature switches (sensors) TS...-ATEX and TF...-ATEX. All temperature switches (sensors) types are simple electrical apparatuses without own power supply (according to EN 50020 and EN 60079-14). In potentially explosive gas atmosphere (hazardous areas) all temperature switch (sensor) types have to be used only in intrinsically save electric circuits (take care of requirements of EN 60079-14 and technical specifications). The equipment is made for temperature monitoring of fluids within a reservoir. For this, temperature-contacts or PT100 sensors are positioned inside the tube. The temperature switches (sensors) are supplied completely assembled and ready for installation. Use the male thread at temperature switches (sensors) for mounting.

Temperature sensor TF-M-Pt100 / TF-E-Pt100: The temperature sensor Type TF contains a Pt100 sensor according to DIN / IEC 751 Class B having a temperature depending resistance. The Pt100 Sensor is placed at the lowest point of the sensor tube to ensure a steady contact with the medium to be measured.

Bi-Metal temperature switch TSM / TSE / TSK / TSA: The temperature sensor TS uses a bimetal-temperature switch to signal a selected temperature value. Compared to the standard version TSM and TSE the TSK and TSA versions with bi-metal switch have a lower hysteresis. Furthermore the version TSA is specially adapted for installation in tube systems and cooling matrices. The bimetal switch is placed at the lowest point of the sensor tube to ensure a steady contact with the medium to be measured. 14.2 Included items in delivery

E-mail: [email protected] BX140010

Page 15: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

15

- Temperature switch TSM-Atex, TSE-Atex and TSA-Atex

- Temperature sensors TF-M-ATEX and TF-E-Atex quantity part-no

1.) Installation and Operation Instruction BX140010 1 9032012

2.) Elastic gasket G1/2 (NBR) 1 1120101

- Temperature switches TSK-ATEX 1.) Installation and Operation Instruction BX140010 1 9032012

2.) Elastic gasket G3/4 (NBR) 1 1120102

15. Transport and storing regulations The equipment should be only transported in the original case or in appropriate packing. Protect the temperature switches (sensors) against heat and humidity. The temperature switch (sensor) must be stored in roofed, dry, vibration- und dustfree room. Temperature should be between –20°C and +40°C. 16. Installation and connection 16.1. Mounting The temperature switches (sensors) are supplied completely assembled and ready for installation. Use the male thread of the temperature switches (sensors) for mounting.

The maximal starting torque for the inscrewing thread is 25Nm. During installation take care that the gasket surface is clean and plane and that the temperature switch (sensor) is only screwed in at the appropriate thread. The gasket consists of an elastic gasket ring. Other gasket material is not needed. Wiring diagrams and technical data can be found in the appendices (page 20-22). 16.2. Electrical connecting (intrinsically safe) Choose the wiring diagramm for your temperature switch (sensor) from page 19. Read the electrical data on the data sheet of your temperature switches (sensors). Please note that all temperature switches (sensors) have a PA-connection (PA=potential equalization). You have to connect the PA-connection of the temperature switch (sensor) to your grounded reservoir. Attention !

!

The connection to the electrical mains must be made according to local regulations.

16.2.1. Intrinsically safe connection All temperature contacts as well as Pt 100 have to be connected intrinsically safe. Take care of EN 60079-14 and directive 94 / 9 / EC. The permissible maximum-current for temperature-contacts is Imax = 90 mA (at Umax up to 30VDC). The permissible maximum-current for Pt100 is 1 mA (max. input power Pi = 0.14 mW) Attention !

!

Intrinsic safety Equipment for potentially explosive atmospheres (hazardous areas) have to be used only in intrinsically save electric circuits (take care of requirements of EN 60079-14 and technical specifications in this instruction manual).

17. Operation and maintenance

E-mail: [email protected] BX140010

Page 16: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

16

17.1 Indication of risk

Attention !

!

The temperature switches (sensors) should not be operated out of the range of its specifications.

Attention !

!

Any manipulation on the temperature switches (sensors) which is not described in this manual should only be excecuted by Bühler authorizised staff. Only perform modifications, servicing or mounting which is described in the manual. Only use original spare parts.

Attention !

Electrical connections Before any manipulation on the temperature switch (sensor), disconnect the electrical equipment from the main power supply. Make sure that the electrical equipment cannot be reconnected with mains supply. The wiring must be done by trained staff only.

Attention !

!

Intrinsic safety Temperature switches (sensors) for potentially explosive atmospheres (hazardous areas) have to be used only in intrinsically safe electric circuits (take care of requirements of EN 60079-14 and technical specifications in this instruction manual).

Attention !

Corrosive Protect yourself against toxic / corrosive gas during maintenance. Use gloves, gas mask and face protector under certain circumstances.

Attention !

!

Regard the corresponding safety and operation regulations during maintenance.

Attention !

!

Electrostatic charge Clean plastic parts and labels with damp cloth only.

Attention !

!

Electrostatic discharge Use equipment only in areas where ignitable electrostatic discharges can not occur frequently during normal operation.

E-mail: [email protected] BX140010

Page 17: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

17

Attention !

!

Spark formation Protect the equipment against being hit.

17.2. Check before operation Please: - Check all electric connections, make sure there is no damage and mounting is correct. - Make sure no part of the temperature switches (sensors) is demounted. - Check whether the temperature switch (sensor) is connected intrinsically safe - Check whether the protective and surveillance devices are installed and functioning ( e.g.: switch amplifier) . - Check that the ambient parameters are not exceeded (e.g. : Imax, Umax, Pi‘). - Verify compliance with the data on the type plate! - Check that all electrical connections are tightened; check if the monitoring equipment is properly connected and set! - Check whether equipment is grounded and duly protected! - Check whether the connector plug is closed; check if the cable entry points are properly sealed. - take care of EC directive 94 / 9 EC (and EN 60079-14) Please regard the technical specifications of the temperature switches (sensors) and the wiring diagrams in chapter 21. Please regard also the indications of risk in chapter 12 and 17.1. 17.3 Maintenance If the devices are installed and connected in accordance to the mentioned instructions there is no need for regular maintenance. 18. Trouble shooting and elemination Attention !

!

In case of failure switch of the equipment immediately and it should not be turned on again before elimination of the damage.

19. Repair and disposal In case of failure during operation do not hesitate to contact with our service team

phone-number: +49-(0)2102-498955 or our local distributor.

In case of fundamental failure the probe must be checked by the manufacturer. Please send the equipment in an appropriate packing back to

Bühler Technologies GmbH - Service – Harkortstraße 29 D-40880 Ratingen

19.1. Disposal The corresponding laws and regulations of your country must be followed by disposal.

E-mail: [email protected] BX140010

Page 18: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

18

20. List of chemical resistance

material HLP / HVLP HFA HFC HFD-R HFD-U HETG HEES

aluminium, unprotect j n*1 j j j j j

aluminium, anodized j j j j j j j

steel black St37 j n*1 j j j j j

steel galvanizes j n*1 n n n n n steel galvanizes – chromatized j j j n n j j

cast iron GG j n j j j j j

cast iron GGG j n j j j j j stainless steel 1.4301 j j j j j j j

polyamide 6.6 j j j j j*5 j j

tin j j n*5 n n

brass j n*1 n *1 j j j HI 16 (ground coat blue)

TGIC-PET-powder j n j j j

Material HEPG kerosene skydrol DOT 4 methanol ethanol aluminium, unprotect j n j*5 n j

aluminium, anodized j j j*5 n j

steel black St37 j j j*5

steel galvanizes j n j*5 steel galvanizes – chromatized j j j*5

cast iron GG j j

cast iron GGG j j stainless steel 1.4301 j j j*5 j j

polyamide 6.6 j j j*5

tin n j

brass j j*5 HI 16 (ground coat blue) n

TGIC-PET-powder n n *1 = constant conditional, *5 = data oil-supplier

E-mail: [email protected] BX140010

Page 19: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

19

21 Anhang Appendix

21.1 Anschlußbelegungen / Wiring diagrams

Hinweis: Bei Sondertypen können evtl. von den folgenden Anschlußbildern abweichende Anschlußbelegungen vorkommen. Beachten Sie in diesem Fall die mit den jeweiligen Sondertypen mitgelieferten Anschlußbelegungen.

Note: By some special types can be changed the wiring diagram. In this case, please use the wiring diagrams in the additional documentation.

Temperaturfühler / temperature sensor TF-M-Pt100 / TF-E-Pt100 Mit Stecker M3 nach DIN 43650 Mit Stecker M12 With connector M3 according to DIN 43650 With connector M12

v

PT1002

3PE

1 234

1

F000

421X

v

PT100

PE Bi-Metall Temperaturschalter / Temperature switch TSM / TSE / TSK / TSA: Mit einem Temperaturkontakt With one temperature contact Mit Stecker M3 nach DIN 43650 Mit Stecker M12 With connector M3 according to DIN 43650 With connector M12

F000

422X

2

3PE

1 423

1

PE

T11 T1

Mit zwei Temperaturkontakten With two temperature contacts

Hinweis! T1 kennzeichnet den Temperaturkontakt mit der niedrigen Schalttemperatur T2 kennzeichnet den Temperaturkontakt mit der höheren Schalttemperatur Note! T1 is the temperature contact with the lower switching temperature T2 is the temperature contact with the higher switching temperature

Mit Stecker M3 nach DIN 43650 Mit Stecker M12 With connector M3 according to DIN 43650 With connector M12

F000

423X

2

3

PE

1 4

23

1

PE

T11 T1

T2 T2

E-mail: [email protected] BX140010

Page 20: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

20

21.2 Informationen zum PA-Anschluß (Potentialausgleich) Alle Temperaturschalter (-fühler) haben einen externen PA-Anschluß. Dieser ist am rechts dargestellten Aufkleber zu erkennen. Der Anschluß erfolgt mittels Gewinde M4 Das PA-Kabel für den Potentialausgleich zwischen Temperaturschalter (-fühler) und Tank ist nicht im Lieferumfang enthalten und muß vom Kunden beigestellt und angebracht werden Ein Beispiel für den PA-Anschluß ist in Skizze A anhand des TSK-1-Atex-G3/4-M3 dargestellt:

F000403X

Some information about PA-connection (PA = potential equalization) All temperature switches (sensors) have a external PA-connection. You discern it by adhesive label such on right side. They have connecting M4. The PA-cable for potential equalization between temperature switches (sensors) and reservoir is not part of delivery and have to fitted by customer. For example of a PA-connection see sketch A of a TSK-1-Atex-G3/4-M3.

F000403X

Skizze A / sketch A

Temperaturschalter TSK-Atex

PA-Anschluß am Temperaturschalter /PA-connection temperature switch

PA - Aufleber /PA - adhesive label

PA-Kabel / PA-cable

Tank / tank

PA-Anschluß am Tank /PA-connection tank

F000419X

Achtung !

!

Elektrostatische Aufladung Temperaturschalter (-fühler) -Gehäuse müssen mit einem externen PA-Anschluß am Tank verbunden werden !

Sorgen Sie bitte für eine ausreichende Erdung (Mindest-Leiterquerschnitt 4mm2) der Temperatur-schalter (-fühler).

Beachten Sie insbesondere auch die Anforderungen der EN 60079-14 (″Errichtung elektrischer Anlagen in explosionsfähiger Gasatmosphäre″). Attention !

!

Elektrostatic charge of ungrounded housings Connect the housing to a external PA-connector.

To prevent charging of the temperature switch (sensor), connect the housing (minimum conductor cross section = 4mm2) to the grounding connection. Please take also notice of the requirements of EN 60079-14 (NF C23-579-14) and directive 94/9 EC.

E-mail: [email protected] BX140010

Page 21: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

21

Aufbau des PA-Anschlußes bei Temperaturschaltern (Fühlern) / Structure of PA-connection at temperature switch

1. Schraube /

2. Fächerscheibe /

3. Unterlegscheibe /

4. PA-Kabel (ist Kundenseitig anzubringen) /

5. Unterlegscheibe /

screw

lock washer

ring washer

PA-cable ( fitted by customer)

ring washer

4 2

F000420X

5 3 1 21.3 Technische Daten zu Temperaturkontakten und Pt100 /

Technical datas temperature contacts and Pt100 Temperaturkontakte / Temperature contacts Typ type TMÖ TMS TKÖ TKS Funktion function

Öffner / normally closed

(NC)

Schließer / normally open

(NO)

Öffner / normally closed

(NC)

Schließer / normally open

(NO) Betriebsspannung max. max. operating voltage 30 V DC

I max. 90 mA

Li; Ci vernachlässigbar

negligible Wiederstandsthermometer Pt100 / Temperature sensor Pt100 Fühlerelement Temperature sensor

Pt100 Klasse B DIN / IEC 751 Pt100 class B DIN / IEC 751

Toleranz tolerance ± 0,8 °C

Pi 0,14 mW

I max. 1 mA

Li; Ci vernachlässigbar

negligible Grundwerte der Meßwiderstände Pt100 / basic numbers of precision resistor Pt100 °C 0 10 20 30 40 50 60 70 80 90 100 Ohm 100,00 103,90 107,79 111,67 115,54 119,40 123,24 127,07 130,89 134,70 138,50

E-mail: [email protected] BX140010

Page 22: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter TS- ATEX / Temperature sensors TF- / Temperature switches TS-ATEX

Version 1.0, 11/2004, Art.Nr.: 9032012 Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20 Internet: www.buehler-technologies.com

22

21.4 Technische Daten zu den Steckern Technical datas connectors

Stecker / connectors Typ type

M3 3 pol.+PE DIN 43650

M12 4 pol.+PE

Schutzart protection class IP65 IP67**

Kabelverschraubung cable gland PG 11 PG 7**

Betriebsspannung max. max. operating voltage 30 V DC

I max. 90 mA ** mit zugehörigem Steckeroberteil ** with plug fixed 21.5 Technische Daten zu den Temperaturschaltern, -fühlern

Technical datas temperature switches Größe des Einschraubgewindes / size of fixing thread TSM, TSE, TF-M,TF-E,TSA = G1/2 TSK = G3/4

Technische Änderungen vorbehalten. We reserve the right to amend specifications.

E-mail: [email protected] BX140010

Page 23: Bedienungs- und Installationsanleitung Installation- and ... · Bedienungs- und Installationsanleitung Installation- and Operation Instruction Temperaturfühler TF- / Temperaturschalter

EU-Konformitätserklärung gemäß EN 45014EU-declaration of conformity according to EN 45014

12.04Bühler Mess- und Regeltechnik GmbH, Harkortstr. 29, D-40880 Ratingen,

Tel. +49 (0) 21 02 / 49 89-0, Fax. +49 (0) 21 02 / 49 89-20Email: [email protected]

KX 10 0011

Hiermit erklären wir, dass die nachfolgenden Produkte den wesentlichen Anforderungen der folgendenRichtlinien in ihrer aktuellen Fassung entsprechen:- Richtlinie 73/23/EWG über elektrische Betriebsmittel zur Verwendung innerhalb bestimmter

Spannungsgrenzen- Richtlinie 89/336/EWG über die elektromagnetische Verträglichkeit- Richtlinie 94/9/EG über ExplosionsschutzHerewith we declare that the following products correspond to the essential requirements of- Directive 73 / 23 EWG about electrical equipment for use with certain limits of voltage,- Directive 89 / 336 / EWG about electromagnetic compatibility,- Directive 94/9/EC about explosive atmospheres

Produkte / products

Temperaturschalter (Fühler)(Temperature switch (sensor))

TS... - ATEXTF... - ATEX

Die Erklärung gilt für alle Exemplare, die nach den beim Hersteller hinterlegten Fertigungsunterlagen - dieBestandteil dieser Erklärung sind - hergestellt wurden.Bei den Temperaturfühlern TF...-ATEX und Temperaturschaltern TS... –ATEX handelt es sich nach DIN EN50020 um einfache elektrisches Betriebsmittel ohne eigene Spannungsquelle, welche für den Tankeinbauoder (ausschließlich bei Typ TSA) für den Einbau in Rohrleitungssysteme und Kühlregister bestimmt sind.Bei eigensicherem Anschluß können sie im explosionsgefährdeten Bereich der Zonen 1 (Gruppe IIC)installiert werden. Sie dienen hierbei zur Temperaturüberwachung von Fluiden.Die Betriebsmittel dürfen nur durch Fachpersonal installiert werden; die einschlägigen Sicherheitsvorschriften(z.B. EN 60079-14) sind zwingend zu beachten.This declaration is valid for all devices manufactured according to the design and manufacturingspecifications of the manufacturer. These specifications are part of this declaration.Temperature sensors TF...-ATEX and temperature switches TS...-ATEX are simple apparatuses according toDIN EN 50020 made for tank top mounting or (only Type TSA) installation in tube systems and coolingmatrices. In case of intrinsically safe connection they can be used in Zone 1 (group IIC) of Ex-areas.They are made for temperature monitoring of fluids within a reservoir.The equipment has to be installed by trained personnel. All safety regulations have to be fulfilled.

Zur Beurteilung der Konformität wurden folgende harmonisierte Normen in aktueller Fassung herangezogen:The following harmonized standards in actual revision have been used:

EN 61000-6-3 Elektromagnetische Vertäglichkeit- Fachgrundnorm Störaussendung (Wohnbereich,Geschäfts und Gewerbebereich, Kleinbetriebe) EN 61000-6-2 Elektromagnetische Störfestigkeit- Fachgrundnorm Störfestigkeit (Industriebereich)EN 60204 –1 Sicherheit von Maschinen - elektrische Ausrüstung von Maschinen – Teil1EN 50014 Elektrische Betriebsmittel für explosionsgefährdete Bereiche - Allgemeine BestimmungenEN 50020 Elektrische Betriebsmittel für gasexplosionsgefährdete Bereiche – Eigensicherheit „i“EN 1127-1 Explosionsfähige Atmosphären, Explosionsschutz, Teil1: Grundlagen und MethodikEN 13463-1 Nichtelektrische Geräte für den Einsatz in explosionsgefährdeten Bereichen, Teil 1prEN13463-5 Nichtelektrische Geräte für den Einsatz in explosionsgefährdeten Bereichen, Teil 5

Ratingen, den 07.12.2004 Jahr

________________________ __________________________________G.R. Biller Stefan EschweilerGeschäftsführer – Managing Director Technischer Leiter – technical manager