MOVOTRAC 07B mit Profibuskarte DFP21B, DFP11B Safty MOVOTRAC 07B mit ProfiNetkarte DFE32B, DFS21B Safty Description of the interfaces for Movitrac 07B Item number: 4-800-044-1xxx - safty stop (STO) PLd EN ISO 13849-1 - Fieldbus interface Profibus (DFP21B, Safe DFS11B) ProfiNet (DFE32B, Safe DFS21B) DeviceNet (DFD11B) EtherCAT (DFE24B) EtherNet und Modbus/TCP (DFE33B Movi-PLC (DHP11B) - switching fast/slow - Temperature evaluation (TH/TF) - between position Approach

MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

MOVOTRAC 07B mit Profibuskarte DFP21B, DFP11B Safty

MOVOTRAC 07B mit ProfiNetkarte DFE32B, DFS21B Safty

Description of the interfaces for Movitrac 07B

Item number: 4-800-044-1xxx - safty stop (STO) PLd EN ISO 13849-1 - Fieldbus interface Profibus (DFP21B, Safe DFS11B) ProfiNet (DFE32B, Safe DFS21B) DeviceNet (DFD11B) EtherCAT (DFE24B) EtherNet und Modbus/TCP (DFE33B Movi-PLC (DHP11B)

- switching fast/slow - Temperature evaluation (TH/TF) - between position Approach

Page 2: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 2 of 25

Translation of the description of the interfaces You are not permitted to provide this information to either third parties or competitors without our express, written permission!

Subject to change without notice.

Contents

Contact person: ................................................................................................................................. 3

Safety information ............................................................................................................................. 4 Symbols used ............................................................................................................................................................ 4

Safety information for electrical equipment for use in industrial power plants ............................ 4

Description inputs and outputs of the bytes ................................................................................... 9

Description of the software procedure ........................................................................................... 11 Procedure ................................................................................................................................................................ 11

Variant moving to intermediate position ........................................................................................ 12

Additional notes for selection “slow/fast” via input DI12 ............................................................. 12

Start-up information - please observe! ........................................................................................... 13

Description of the inputs and outputs ............................................................................................ 13

Warning notices ............................................................................................................................... 13

Device faults F-XX and parameter settings .................................................................................... 14

Link SEW documents ...................................................................................................................... 14

Sequence diagram ........................................................................................................................... 15

Sequence diagram shuttle operation ............................................................................................. 16

Wiring diagram 3-phase without STO (safety stop) ....................................................................... 17

Wiring diagram 3-phase with STO (safety stop) ............................................................................ 18

Layout ............................................................................................................................................... 19

EM turns in permanent condition and does not stop anymore. ................................................... 20

Example project for TIA-Portal profibus-interface ......................................................................... 21

Example project for STEP7 classic profibus-interface .................................................................. 23

Please refer to the Movitrac07B operating instructions for additional information (see the attached document for the frequency converter)

SEW

Page 3: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 3 of 25

Contact person:

Mr. Schmitt Tel.: 0049(0)7134-73296 email: [email protected] Mr. Neufeld Tel.: 0049(0)7134-73476 email: [email protected]

FIBRO GmbH Rotary Table Division Postfach 11 20 74183 Weinsberg, Germany Weidachstr. 41 -43 74189 Weinsberg, Germany

Service email [email protected] Tel. +49(0)7134 / 73 - 243 FAX +49(0)7134 / 73 - 344

Erstellt am: Januar. 2016 Überarbeitet am : April 2018

Page 4: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 4 of 25

Safety information

Safety

Symbols used

DANGER

Indicates an immediately dangerous situation! Failure to observe this warning will result in a fatal or serious injury.

WARNING

Indicates a possibly dangerous situation! Failure to observe this warning may result in serious injuries or death.

NOTE

Provides information, tips, and recommendations that are important for the safety and proper functioning.

Safety information for electrical equipment for use in industrial power plants

This information sheet with the warnings is considered a supplement to the product-specific operating instructions and must be paid particular attention for reasons of safety.

DANGER

DANGER!

The electrical machines or devices are operating equipment for use in industrial power plants. During operation, this equipment has dangerous, live, bare parts, and also moving or rotating parts, if necessary. They could cause severe physical injury or material damage, for example, if the required covers are improperly removed, if used improperly, incorrect operation or insufficient maintenance.

For the safety of the system, the responsible persons must therefore ensure that only qualified persons are contracted to perform work on the machine or devices; these persons must have the supplied operating instructions and other necessary documents of the product documentation always available during all corresponding work and are obliged to observe the information in these documents consistently; unqualified persons are forbidden from performing work on the machine or equipment or working in its vicinity.

Page 5: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 5 of 25

Qualified personnel are persons who, due to their education, experience, training, as well as their knowledge of pertinent standards, provisions, accident prevention regulations, and company conditions, have received authorisation from the persons responsible for the safety of the system to perform the required tasks whilst recognising and preventing possible dangers (for the definitions of expert personnel, also see VDE 0105 or IEC 364). This includes but is not limited to having knowledge of first-aid measures and local rescue facilities. For work on high-voltage systems, the prohibition of the use of unqualified personnel is regulated in DIN VDE 0105 or IEC 364, for example.

DANGER

DANGER!

► The fundamental planning work of the system, as well as all work with regard to transport, assembly, installation, commissioning, maintenance and repair must be performed by qualified personnel and inspected by responsible specialized personnel.

► In particular, the following must be observed:

Technical data and specifications about the permitted use (assembly, connection, environmental and operating conditions, and requirements) which, among others, are contained - in the catalogue - the order documents - the operating instructions - the rating plate data of the remaining product documentation.

► The general set-up and safety regulations, the local system-specific

conditions and requirements, the proper use of tools, lifting and transport equipment, the use of personal safety equipment, assembly requirements for devices, which are supplied, if necessary, corresponding to IP00 (without cover):

► During operation, the required protection against accidental contact must

be present, respectively, a dangerous proximity must be prevented.

NOTE

For reasons of clarity, the operating instructions are not able to include all detailed information about possible versions and are not able to take into account every conceivable case with regard to setup, operation or maintenance.

Accordingly, the information contained in the operating instructions only contains information about the proper use of the machine or equipment in industrial areas of application which is required for qualified personnel (see above). If higher requirements are placed, for example, in special cases for an intentional use of the machinery or equipment in non-industrial areas (e.g. prevention of contact by children's fingers or similar), the fulfilment of these additional requirements must be ensured during the assembly by the provisioning of additional safety measures on the system.

Page 6: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 6 of 25

For any lack of clarity with regard to this, particularly with regard to missing product-specific detailed information, the required clarifications must be obtained. For these types of queries, please always specify the machine type designation and manufacturing number.

NOTE

We recommend obtaining support from the FIBRO Service Department for service tasks.

WARNING

SWITCH OFF THE EQUIPMENT IMMEDIATELY IN CASES OF DOUBT!

The contents of these operation instructions and product documentation shall not become part of or modify any prior or existing agreement, commitment or legal relationship. All obligations of FIBRO result from the underlying purchase contract, which also contains the complete and solely valid warranty regulation. These contractual regulations are neither amended nor limited by the descriptions contained in these operation instructions and documentation.

NOTE

Information about the observance of accident prevention regulations

NOTE

For general work, e.g. incoming shipments (transport damage), for long-term storage and preservation of machines, for foundation inspection, for mounting of couplings, setting up and aligning machines, installation measures etc., you can find detailed information in the operating instructions. If necessary, you can also obtain this from the distributors.

WARNING

WARNING!

► To prevent malfunctions, the stipulated maintenance, inspection, and overhaul measures must be performed regularly by experienced service personnel (see above).

► If changes to normal operation (higher current consumption, temperatures, vibrations, noises etc. or the activation of monitoring equipment) are noticed, this may indicate an impairment of the function. The responsible maintenance personnel must be notified immediately in such cases to prevent malfunctions which could cause an indirect or immediate severe personal injury or damage.

Page 7: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 7 of 25

Since we do not supply an operationally ready machine or system, but rather, a component, we are not able to provide standardised safety equipment without knowledge about the rotary indexing table environment. Our accessories program includes different covers over toothed belts, V-belts, chains, and end-switch actuation, either for the purposes of contact protection or also in sealed design for all sizes and drive versions. If you have ordered the rotary table without sufficient safety equipment, you must absolutely provide for this yourself. Due to the previously mentioned reasons, we would like to again point out that we shall not accept any claims directed towards us that arise from non-observance of the accident prevention regulations in question. Also outside of our scope of responsibility are cutting and crushing hazards which arise through drill holes or other openings, both through the table top as well as through the underlying or overlying fixed table plate.

This sheet was already sent to you with the order confirmation.

WARNING

WARNING!

► The switch cabinet contains electrical devices and components of these electrical devices with live dangerous voltages. Improper use of these devices can therefore lead to death or severe personal injury or damage.

► Installation and commissioning may only be performed by qualified, trained, and instructed electricians. These persons must be fully familiar with the content of these instructions.

► The precise knowledge of the operating instructions, the circuit

diagram, the control system manuals, as well as the operating instructions of the rotary table is a requirement for a trouble-free continuous operation

Page 8: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 8 of 25

An explanation about the operating device is included with every frequency converter. FIBRO SCOPE

Display ramp up Display ramp down Setpoint adjuster Fixed preset value Maximum preset value Parameter Setup motor commissioning Data backup Selection setpoint adjuster

Page 9: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 9 of 25

Description inputs and outputs of the bytes

ATTENTION!!!

The proximity switches –S10 and –S12 should be directly wired in the hardware, provided that the transfer time of the

field bus is above >20ms! Consequence – holding in the holding phase is no longer possible.

GSD file configurator.

Reading the identifier AS 1 Drive (3PD) as configuration

Data from PLC to FU These are 3 data words that have to be allocated as follows:

Byte 1 0000 0000

Byte 2 0000 0110 Hex 6 is required in order to establish a communication. statical

Start of edge only after right or left has been preselected

Proximity switch via PLC -S10 “indexing table in standstill” (If Not wired on FU)

Proximity switch via PLC –S12“moto off” (If Not wired on FU)

Preselection clockwise

Preselection counterclockwise

Stop

Reset

Changeover fast = 1, slow = 0

Move to intermediate position = 1

Proximity switch intermediate position –S13 (intpos)

7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Communication 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Examplesclockwise 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 1 0 0 0 1 1

counterclockwise 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 1 0 0 1 0 1

both right and left

stop 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 1 0 1 1 0 0

reset 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 1 1 0 1 0 0

slow 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

intermediate position 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 1 0 1

Start from intpos 0 0 0 0 0 1 1 0 0 0 0 0 0 0 1 0 1 0 0 1 0 1

Byte 2 Byte 5 Byte 6

Page 10: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 10 of 25

Data FU to the PLC These are 3 data words that are allocated as follows:

DO01Safety stop

DO02 ready=1, fault=0

DO03 Enable to the PLC

Proximity switch –S10 “indexing table in standstill”

Proximity switch –S12 “motor off”

Proximity switch _S13 “moved to intermediate position”

Drive (0=turning, 1=standstill)

7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

BTB / release 0 0 0 0 0 0 1 0 0 0 0 0 0 1 1 0 X 1 1 1 0 0

rotary table turning 0 0 0 0 0 1 1 1 0 0 0 0 0 1 0 0 1 X 0 1 0 0

start after error 0 0 0 0 0 1 0 0 0 0 0 0 0 1 1 1 1 X 0 0 0 0

STO 0 0 0 1 0 0 0 1 0 0 0 0 0 1 0 0 X X 1 0 1 0

S10/S12 Low 0 0 0 0 0 0

left/right High 1 0 0 0

left/right Low 0 0 0 0

moved to intpos 1

ErrorF-31 0 0 0 1 1 1 1 1

STO 0 0 0 1 0 0 0 1

Byte 1 Byte 2 Byte 6

X = can be high(1) or low(0)

Reflection of the signals from PLC to FU

7 6 5 4 3 2 1 0

Byte 5

start selected 0 0 0 0 0 0 0 1

clockwise selected 0 0 0 0 0 0 1 0

countercklockwise selected 0 0 0 0 0 1 0 0

stop selected 0 0 0 0 1 0 0 0

reset selected 0 0 0 1 0 0 0 0

fast selected 0 0 1 0 0 0 0 0

intermediate position selected 0 1 0 0 0 0 0 0

Page 11: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 11 of 25

Description of the software procedure

General

By means of an internal FIBRO SOFTWARE PROGRAM, we can operate the rotary table FIBROTOR via the Profibus and 2

outputs with the frequency converter.

The frequency converter has been pre-set suitably to the rotary table at FIBRO.

The software is written in a way that the maximum or minimum rotational speed is driven via the control, depending on the

procedure situation.

Procedure

Via selecting DI12 (fast/slow) and DI01 “Turn clockwise” or DI02 “Turn counterclockwise” and pending signal of the

proximity switch DI04 “-S10 indexing table in standstill”, as well as pending signals via the outputs DO03 “Release for

processing” and DO02 “Ready for operation/malfunction”, one can realise a turning movement via a stroke by means of a

start signal DI10 “Start”. After the start signal, the output DO03 is taken away. As soon as it arrives again on the proximity

switch DI04 “-S10 indexing table in standstill”, the output DO03 “Release for processing” is reported as high signal. From

this signal, you can start externally! The output is realised via the cam ”-S10 indexing table in standstill”.

In case of overrun of the rotary table, the output DO03 “release for processing” is taken away!

Via the input DI03”-S12 motor off”, the rotary motion is stopped and the output DO03, after which the input DI04 is pending,

is set. After a renewed start signal, the next rotary motion is carried out.

The output DO03 “Ready for operation” has a set output signal, as soon as no malfunction is pending.

Malfunction D02

If no signal is present at the output DO02 “Ready for operation/malfunction”, then a malfunction has been caused!

A malfunction can be: - both proximity switches have no signal

- safe stop (STO)

- right/left both active

- device error F-08 (current limit, parameter 303), TH/TF (temperature motor) see operating unit

SEW

- Stop input DI11 “stop” wired

At the signal aspect, no signal at DI04 ”-S10 indexing table in standstill” and DI03 ”-S12 motor off”, a rotary motion cannot

be initiated. Here, a mechanical intervention or a check of the cam adjustment with the function of the proximity switches is

required.

Stop input DI11

Here, the rotary table is stopped during its turning phase! Must also be wired at emergency stop and safe stop (STO)!

The rotary table does not turn, as long as the stop input is pending!

Reset input DI00

Malfunction=0/Ready for operation=1 (At device fault F-XX see error code in the SEW documents!)

At each malfunction DO02 “Ready for operation/malfunction”, the malfunction is reset via the input DI00 ”reset”, if a

device fault is no longer present!

EMERGENCY STOP circuit!

When an emergency stop loop is integrated, the power must be shut of between FU and three-phase brake motor, and the

inputs DI01 (clockwise), DI02 (counterclockwise) and DI03 (start) must be disconnected from the mains. After the emergency

stop loop has been reconnected, you can continue the rotary motion as described in the section “Procedure”.

Stop input DI04!

Here, the rotary table is stopped during its turning phase! Must also be wired at emergency stop and safe stop!

The rotary table does not turn, as long as the stop input is pending!

Page 12: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 12 of 25

Variant moving to intermediate position

Procedure

By means of the input “DI13” preselection intermediate position; you activate the program for moving to this intermediate

position in creep speed.

The following wiring is necessary for moving to the intermediate position.

- Set DI13 to “high”

By means of DI10 “Start”, the rotary table moves to the position DI16 “-S13 intermediate position”

When the intermediate position is reached via the proximity switch “–S13 intermediate position”, DO03 is set to “high”,

and output DO02 is set to “low”.

Output message:

- DO02 low signal = no malfunction, a malfunction is caused here!

- DO03 high signal = release

In order to leave the intermediate position and to get back to a “right/left” initial position,

DI13 “Preselection intermediate position” is set to Low, DO03 goes off and by means of the input DI00 “Reset”

the created error is reset and with the selection DI01 or DI02 “right or left” and with a start DI10, the table moves to the initial

position.

Output message at right/left operation

- DO02 high signal = no malfunction

- DO03 high signal = release

Behaviour in case of malfunction

Proximity switch –S13 intermediate position defective

Rotary table turns until the next position.

Output message

- DO02 low Signal = no malfunction

- DO01 low Signal = release

Check the proximity switch!!

Move again into a new position!

First possibility: -- move once more to the intermediate position

Second possibility: -- turn either clockwise or counterclockwise.

Additional notes for selection “slow/fast” via input DI12

If the input DI10 is wired, then the table turns with the set maximum rotational speed, which is set in the parameter 160. To the intermediate position If the input DI10 is not wired, then the table turns with the minimum rotational speed, with is set in the parameter 161.

Additional adjustment of the rotational speed Via the parameter (160 “Internal nominal value N11”(fast) and the parameter 161 “Internal nominal value N12”(slow)), the rotational speed can be subsequently reprogrammed. Do not make this adjustment without consulting the company FIBRO.

Integrated control panel Operation only by qualified personnel. After an untrained intervention, a smooth operation can no longer be guaranteed. In this case, we are not liable for damages.

Page 13: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 13 of 25

Start-up information - please observe! The start-up engineer must program a time monitoring parallel to the movement. The time monitoring should also be tested, so that this time monitoring is adjusted also after an emergency stop. If the rotary table procedure is not realised within this time period, then one must disconnect the voltage from the inputs. (low wiring)

Description of the inputs and outputs

Wired inputs Fieldbus addresses X12

Via the bus system DI00 reset byte 6 0100 0000

DI01 turn clockwise byte 6 0000 1000

DI02 turn counterclockwise byte 6 0001 0000

Optional

DI03 -S12 motor off Caution!

possibly wiring of the hardware

byte 6 0000 0010 4

DI04 -S10 indexing table in standstill

Caution! possibly wiring of the hardware

byte 6 0000 0100 5

DI05 TH/TF evaluation 6/7

DI10 start byte 6 0000 0001

DI11 stop byte 6 0010 0000

DI12 changeover fast (1) - slow (0), byte 6 1000 0000

DI13 preselection moving to intermediate position byte 5 0000 0001

DI14

DI15

DI16 -S13 proximity switch intermediate position

byte 5 0000 0010

Wired outputs

DO01 safe stop byte 6 0000 0010

DO02 ready for operation=1/malfunction=0 byte 6 0000 0100

DO03 release (release for processing for external machine) byte 6 0000 1000

Warning notices

The exact knowledge of the operating instruction, of the circuit diagram, the manuals of the control unit, as well as of the operating instruction of the rotary table before starting up the plant is the prerequisite for a troublefree continuous operation. We reserve all rights according to DIN 34-1-0. Subject to technical modifications!

Page 14: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 14 of 25

Device faults F-XX and parameter settings

Error indication on the display. For error description see operating instruction “Movitrac B” by company SEW. Example: Malfunctions that have to be readjusted without mechanical intervention, for example “Parameter changes afterwards”, for the adaptation of the rotary table. Common mistake "F-08"! This error occurs when a larger mechanical current is required! In most cases, you can remove it by means of the parameter "303" by increasing the current setting! Factory setting FIBRO according to measurement data and increase of 10% of the parameter "303" Shipped! What is also a measure, the parameter "441"(delay time) should be increased! After the error has been remedied, if this has not already been made by switching off the FU, one must actuate the button on the operator display. Afterwards, actuate the button . Disconnect the input left DI01 or right DI02 and connect them again, thereafter one can move to the initial position by means of a start signal DI010.

CAUTION!!!!!!! For safety-related troubleshooting, e.g. mechanical intervention, it is IMPORTANT to switch of the voltage supply of the frequency converter.

Link SEW documents

Page 15: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 15 of 25

Sequence diagram

Page 16: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 16 of 25

Sequence diagram shuttle operation

Page 17: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 17 of 25

Wiring diagram 3-phase without STO (safety stop)

Page 18: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 18 of 25

Wiring diagram 3-phase with STO (safety stop)

Page 19: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 19 of 25

Layout

Page 20: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 20 of 25

EM turns in permanent condition and does not stop anymore.

If the motor is running at half speed, indicated on the display of the FU, and no red dot lights up at the lower right corner of the display, then the software program does not start. Software program is running Software program is not running

Measure: Variant 1: Feed in data via a parameter module. The parameter module must contain the data from a started program. Variant 2: Request a programmed parameter module from FIBRO. Irregular Holding, no start possible: Change Task setting!

Task 1 = 5 parameter 938 Task 2 = 4 parameter 939

Parameter 881 Bus setting to 1

Page 21: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 21 of 25

Example project for TIA-Portal profibus-interface

Now the control and status bits can be used like standard inputs / outputs!

Page 22: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 22 of 25

Variable table for controlling/monitoring the frequency inverter. monitor bits ( inverter PLC )

control bits ( PLC inverter) )

Page 23: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 23 of 25

Example project for STEP7 classic profibus-interface

Data transfer is done in FC100

Page 24: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 24 of 25

FC100

Page 25: MOVOTRAC 07B mit Profibuskarte...SEW . FIBRO GmbH Werk I Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* ... Parameter Setup

FIBRO GmbH Werk I

Postfach 1120 · DE-74183 Weinsberg Weidachstr. 41-43 · DE-74189 Weinsberg Telefon +49 (0 )71 34-73-0* Telefax +49 (0) 71 34-73-120

[email protected] www.fibro.com

Page 25 of 25

Variable table for controlling/monitoring the frequency inverter. status bits ( inverter SPS )

control bits ( SPS inverter )