Pano Kliması
Enclosure Cabinet Cooler
Schaltschrank - Kühlgeräte
Montaj ve Kullanım Kılavuzu
Device Work Schedule
Einbau-und Benutzerhandbuch
www.uludagklima.com info@uludagklima.com
444 3 780
Tel : +90 224 243 70 71 Faks: +90 224 243 88 96
ULUDAĞ PANO KLİMA
SOLUTION OF PROBLEMS
CAUSED BY HEAT Summer months approaches, temperature rises in enclosures (approximately 45-60 °C) with this increase, unscheduled downtime is inevitable. Against to this expected and said "l'M COMING" danger, precautions to be taken is our enclosure cabinet coolers. Uludag enclosure cabinet cooler devices; put an end to breaks in production..! Uludag enclosure cabinet cooler devices; put an end to breaks in production..! During the guarantee period, what may come per unit the unlimited scope of our device is under warranty.When you send the device to our address (without specifying any excuse) failure shall be removed within the same busi-ness day. if the device can not be resolved within 3 business days then new product will be sent to the user. Delivery time is one day in all our products. All sheet metal parts of our products is stainless steel. You can get the smooth automation solutions with using our products equipped with the components known as class A in the world. Danfoss compressors and EbmPapst fans are used on our products.
ULUDAĞ PANO KLİMA
1.ASSEMBLY :
1.1 Fully wired ready for connection, including drilling template, and assembly parts.
1.2 Cut out the sections and drill according to the template.
ULUDAĞ PANO KLİMA
1.3 ASSEMBLY WITH SCREWS Screw tapped pins into the blind nuts on the rear of the unit.
1.4. ENERGIZE THE DEVICE WITH THE SENT CABLE (220 V)
ULUDAĞ PANO KLİMA
2.Product Details :
DIMENSION
X Y Z A B C D E F G H
Svk500 320 228 470 188 164 130 45 115 230 380 188
Svk1000 350 207 695 270 165 193 60 223 27 550 200
Svk2000 400 237 850 250 250 259 70 243 300 650 250
Svk3000 400 258 950 314 210 357 74 272 330 770 254
Svk4000 500 285 1004 224 224 410 90 228
T 2000 400 700 408 230 60 380 60 100 250 613 230
T 4000 444 780 450 250 75 437 75 100 300 700 250
ULUDAĞ PANO KLİMA
Organize Sanayi Bölgesi
Demirciler Sitesi
D Blok No:2
Nilüfer / BURSA / TURKEY
Telefon: +90 (224)23 70 71
Faks: +90 (224) 243 88 96
Tecnic Data Svk-500 Svk-1000 Svk-2000 Svk-3000 T-2000 T-4000
Cooling capacity L35 L35 450 W 1000 W 1700 W 2700 W 1700 W 3700 W
Type of refrigerant R 134a R 134a R 134a R 134a R 134a R134a
Amount of refrigerant 290 gr 410 gr 550 gr 630 gr 630 gr 1150 g
Thermostat setting 34 °C 34 °C 34 °C 34 °C 34 °C 34 °C
Hysteresis 4K 4 K 4 K 4 K 4 K 4 K
External circuit 540 m³/h 540 m³/h 945 m³/h 1175 m3/h 1005 m3/h 1800 m³/h
Internal circuit 290 m³/h 540 m³/h 945 m³/h 945 m³/h 945 m³/h 1175 m³/h
Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Standard power supply 198 V-252 V 198 V…252 V 198 V…252 V 198 V…252 V 198 V…252 V 380 V
Running current 1.6 A 3.2 A 4.2 A 6.5 A 4.2 A 6.8 A
Starting current 5.2 A 16.2A 17.2A 21.2A 17.2A 35,7 A
Weight 19 kg 35 kg 40 kg 45 kg 40 kg 62 kg
Height x Width x Depth mm 470*320*215 670*350*207 850*400*230 950*400*255 410*700*400 445*787*450
Ambient air temperature +15 °C 55 °C
Corrosion protection (cover) Stainless / Paslanmaz Çelik
Orientation Wall Mount Top Mount
System of protection IP 54
Fans EbmPapst
Compressor DANFOSS DANFOSS DANFOSS DANFOSS DANFOSS EMBRACO
ULUDAĞ PANO KLİMA
3.1.CONDENSER CARE 1. Be sure the energy of the device turned
off before open the front door.
2. Clean the condenser with preassured air
from oil,dust etc.(Dirt on the condenser
may couse insufficient heat transfere,
getting failed rapidly and high
energy consumption. Solvent can be used
if contamination is heavy.)
3. Clean the dirt on fan blades. (Dirt cau-
ses to fan balance and to fail in a short
time).
4. Check the drain hose. Remedy the defects
if there are breaks or obstructions.
(Otherwise condensation water may
splash into the panel.)
5. Check the electrical connection cable.
(Abrasion or dislocation may lead short
circuit and fail of the device.)
6. Check the thermostat settings for the device. Be sure the values are adjusted to the recomen-
dation of the seller. (34 ° C - 38 ° C)
7. Turn on the energy after the lid of the device is closed. (Operating the device while lid is open
may cause injuries or malfunction.)
3.MAINTENANCE :
15-day period of your device in the condenser, evaporator care has to be made in annual periods. Depending on the situation of environment pollution, you must specify the period. (May extend or decrease)
ULUDAĞ PANO KLİMA
3.2.Evaporator CARE:
1. Turn off the energy and unscrew
the 8 pcs bolts inside of the device
and remove the fan cover.
2. Clean the oil,dust etc. with preas-
sured air from the evaporator cel-
lular which under the fan engine.
To check the dreinage line’s effici-
ency, pour some water into the
evaporator pan and wach for obst-
ructions.
3. Clean the dirt on fan blades.
4. Check the electrical connection
cable.
5. Replace the fan cover back and
turn the energy on.
6. Check the thermostat settings for
the device. Be sure the values are adjusted to the recomendation of the seller. (34 ° C - 38 ° C)
ULUDAĞ PANO KLİMA
3.3. Before the notify service :
The device does not work? Check electrical connections. Device is receiving power but not working? Check the thermostat
value. (Set value should be below ambient temperature) Device is working. but it does not blow cold air / not enough to blow?
Check that the fan is running clogged evaporator. Clean the evaporator, as described above.
Shortly after the device works, but is disabled? Check the thermostat
value. (Operating temperature range from ambient temperature must be below) Make sure the condenser fan is running. Make sure the condenser is clean If not, see above instructions for cleaning condenser (the high pressure circuit protection may be on.
Device is working. but it does not come from the circuit? Check the
thermostat settings for the device. In the heat value of the firm suggests that you pay attention to (34 ° C - 38 ° C). Ambient air from outside is input to the clipboard, you check. The door panels may be left open.
Important Notice!!! The device is running, the cover must be closed. When you open the lid, turn off power. Otherwise, the environment and the dust will block evaporator
ULUDAĞ PANO KLİMA
4. The DIGITAL SETTING
ADVANCED PROGRAMMING FOR DIGITAL DATA sent as attachments of the document.
ULUDAĞ PANO KLİMA
factory values of parameters
4.3. back to the factory settings for digital:
By holding the up down buttons pressed for 3 seconds when the device is on, then
enter in menu 1 parameters.
1.MENU PARAMETERS DEFAULT
SL1 Set1 value minimum parameter 26
SH1 Set1 value maximum parameter 99
HS1 Hysteresis parameter for compressor 0.1
ASA Waiting mode for elevator application 0
Of1 Off-set parameter for cabin sensor 0
Of2 Off-set parameter for condenser sensor 0
Of3 Off-set parameter for evaporater sensor 0
By holding the reset (R) and SET buttons pressed for 3 seconds, then enter in menu parameters.
2.MENU PARAMETERS DEFAULT
SEn Sensors Active-Cancel parameters 1
HCS Selecting heating/cooling functions 0
Pnt Point position parameter 1
ınt Digital Input Type Selection 0
ıno Digital Input Filter Selection 0
ıPo Digital input polarization 0
CSd Start-Stop Delay Parameters 0
Con Sensor fault ON time 0
CoF Sensor fault OFF time 0
Alo Low alarm fault setting 0.0
Ahı High alarm fault setting 99.9
Cnd Condenser sensor value measured
EuP Evaporater sensor value measured
ULUDAĞ PANO KLİMA
ULUDAĞ PANO KLİMA SİSTEMLERİ
OSB, Minareliçavuş Mh. Türen Sk. No:7
NİLÜFER / BURSA / TURKIYE
TEL: +90 224 243 70 71
FAX: +90 224 243 88 96
www.uludagklima.com
info@uludagklima.com